The i-Grid notifies you within seconds of a power quality event at your location.
Notifications can be customized both in the format of content - from rich text email
to abbreviated mobile formats - and the severity threshold for delivery.
i-Grid's centralized administration makes it simple to configure notifications.
There are no email servers or firewalls to configure.
Rich text notifications include full event details, including waveform and RMS charts.
Hover over information icons or graphics for more information
www.igrid.comPower Quality Event
Immediate Notification
what is this? |
how do I read this?
Location
Name
Location Within Facility
Serial Number
Owner Name
Company Name
Address
480V Service Entrance
NE corner of Bldg
0000-0000-0000
Pat Smith
Rockwell Automation, Inc.
Milwaukee, Wisconsin 53204
Event
Event ID
Start Time
Worst-Case RMS
Nominal Voltage
Duration
IEEE Classification
Frequency
RMS Data
00000
March 14, 2015 @ 9:26:53 AM CDT
69.9V (58.3%)
120.0V
92ms (5.52 cycles)
Instantaneous Sag
60.0Hz
Channel
Min
Max
% Nominal
1
72.9V
117.1V
60.7%
2
109.7V
119.0V
91.4%
3
69.9V
115.6V
58.3%
Charts
Notes
For your records, you can
enter notes about this event's cause and effect
which will be displayed on your summary reports.
00000
March 14, 2015 @ 9:26:53 AM CDT
69.9V (58.3%)
120.0V
92ms (5.52 cycles)
Instantaneous Sag
60.0Hz
You can view more event detail by visiting the i-Grid web site:
http://www.igrid.com/igrid/GetEventDetail.do?serialNumber=0000-0000-0000&eventId=00000&source=email
---------------------------------
i-Grid
Support Line: 440.646.3434 (8am to 5pm M-F, US Central time zone)